Temp ≥100°F → amperios suben a 24A en breaker → salta. Restringe viajes calor.
"When coils dirty no good heat transfer → little refrigerant condensation → condenser coil pressure builds too high → compressor pulls more amps → risks burnout. Either internal protector stops compressor or breaker in generator electrical wiring."
Bobinas limpias → presión condensador normal → amperaje ≤ FLA (ej. 13-15 A) → breaker 20 A no salta. Si amperaje sigue alto → compresor ineficiente (desgastado) o sobrecarga refrigerante.